How ERVs Improve HVAC Efficiency and Indoor Air Quality

Source: Evgenii Bakhchev/stock.adobe.com
Heating, ventilation, and air conditioning (HVAC) systems play a critical role in maintaining clean, comfortable commercial spaces and meeting indoor air quality (IAQ) requirements. Because HVAC equipment often operates for extended periods during hot and cold seasons, energy efficiency remains a key design consideration. Energy recovery ventilators (ERVs) support mechanical ventilation also known as DOAS (Dedicated Outdoor Air System) by supplying outdoor air and exhausting indoor air while using the outgoing airstream to precondition the incoming air’s temperature and moisture content. By reducing the load on heating and cooling equipment, ERVs can significantly improve overall HVAC efficiency. However, achieving these benefits requires careful system design, control, and maintenance.
This blog examines how ERVs enhance IAQ and HVAC efficiency and explains the role of airflow and pressure sensing in maintaining efficient operation.
Understanding ERVs in Commercial HVAC Systems
Indoor commercial environments can accumulate carbon dioxide (CO2), airborne particulates, and gaseous contaminants that degrade occupant comfort, health, and well-being. To maintain acceptable IAQ, ventilation systems must continuously introduce outdoor air while removing stale indoor air. Standards such as ASHRAE 62.1 with their VRP (Ventilation Rate Procedure) procedure set minimum ventilation requirements for commercial buildings, with required ventilation rates varying by factors such as space type, building area, and occupancy levels.[1]
How ERVs Reduce HVAC/DOAS Energy Demand
To meet ventilation requirements, HVAC systems use the demand controlled ventilation (DCV) control strategy to continuously manage airflow as building conditions and occupancy levels change. As a result, many commercial HVAC systems incorporate variable air volume (VAV) systems to monitor and maintain appropriate ventilation rates.
HVAC systems must bring sufficient outdoor air into buildings as conditions and occupancy levels change to meet ventilation requirements, but doing so can create additional challenges. Depending on ambient conditions, incoming air may require heating, cooling, humidification, or dehumidification before it can be supplied to occupied spaces. This continuous conditioning increases HVAC energy consumption and operating costs and can also increase demand on mechanical components such as fans, pumps, and compressors. ERVs can help reduce this load by recovering energy from conditioned air as it is exhausted from the building.
ERVs use outgoing air to precondition fresh air entering from the outside. Inside an ERV, the incoming and outgoing air streams remain separate, but the system transfers energy between them before the indoor air is exhausted from the building. This allows the ERV to recover energy (heat) and latent energy, which is associated with moisture, rather than allowing the energy to leave with the exhaust air.
Energy recovery typically occurs through a rotating enthalpy wheel, a static plate, or a core-based recovery system. In an enthalpy wheel-based ERV, the wheel rotates between the supply and exhaust air streams, absorbing and releasing heat and moisture as it moves between them. The wheel typically contains a material (desiccant) capable of absorbing the humidity in the wet airstream and releasing it in the dry airstream. Static systems keep the two air streams in separate channels within a fixed core, and heat and moisture are transferred through the material separating them. Regardless of the design, the goal is to moderate the temperature and humidity of incoming outdoor air before the HVAC system completes conditioning it.[2]
Energy transfer varies by season. In winter, warm indoor exhaust air transfers heat to the cold, dry outdoor air entering the building. The incoming air is warmer and, in an ERV that transfers moisture, it's also more humid before it reaches the HVAC system. In summer, cooler indoor exhaust air absorbs heat and moisture from the hot, humid outdoor air, so the incoming air is cooler and drier.
The ERV does not replace the HVAC system or even bring incoming air to the desired indoor temperature and humidity. Instead, it reduces the heating, cooling, humidification, and dehumidification required. The preconditioned outdoor air can then be further conditioned by the HVAC distributed through the building’s ductwork.
Maintaining ERV Performance Through Pressure Sensing
For ERVs to operate efficiently, the fans that move air in and out of the ERV housing and heat exchangers must be precisely controlled. This is because the air entering and exiting the ERV must have the proper airflow for the heat exchangers to operate at peak efficiency and achieve the desired air temperature and humidity exchange rates. The indoor and outdoor air temperatures, humidity levels, filter conditions, building occupancy levels, and main HVAC system operation all affect the air conditions for ERVs. Using a differential pressure sensor in an ERV blower control system enables the system to adapt to changes in these conditions with adequate response time to ensure efficient operation. By directly measuring the airflow by methods like a Bernoulli ring at the blower or Pitot Tube in the airduct or inside the ERV the EC motor driving the blower can be controlled to deliver the exact amount of air needed. In comparison to RPM and current based air volume control, true airflow is more accurate, failsafe and precise.
One example of such a sensor is Sensirion’s SDP8xx Digital and Analog Pressure Sensors, which are designed to accurately measure air pressure in high-volume applications without offset drift. These sensors cover typical air-pressure ranges for commercial applications and provide rapid response times for real-time control. The performance advantages of these sensors are enabled by Sensirion's patented CMOSens® sensor technology, which integrates the sensing element, digital calibration, signal processing, and analog output on a compact CMOS chip that is fully calibrated, temperature-compensated, and offers outstanding long-term stability.
High-quality, reliable monitoring of airflow at the ERV’s inputs, outputs, and internal components enables optimized fan speeds in response to changing conditions. With good data collection practices and intelligent control system design, pressure measurements can also reveal trends in ERV operation that indicate the need for service or maintenance. For example, as filters accumulate dirt, the resulting change in pressure can help indicate when they need to be replaced.
Conclusion
Accurate airflow play a key role in maximizing ERV energy efficiency. By transferring heat and moisture between exhaust and incoming air streams, ERVs help maintain indoor air quality while reducing DOAS HVAC energy consumption. Differential pressure sensors support this process by providing the feedback needed to optimize fan operation.
Author
Principal of Information Exchange Services: Jean-Jacques DeLisle
Jean-Jacques (JJ) DeLisle attended the Rochester Institute of Technology, where he graduated with a BS and MS degree in Electrical Engineering. Before completing his degree, JJ contracted as an IC layout and automated test design engineer for Synaptics Inc. Further pursuing his career, JJ moved to New York City, where he took on work as the Technical Engineering Editor for Microwaves & RF magazine. In the next phase of JJ’s career, he moved on to start his company, RFEMX, seeing a significant need in the industry for technically competent writers and objective industry experts. Progressing with that aim, JJ expanded his company’s scope and vision and started Information Exchange Services (IXS).